Section 535-X-11-.10 - Electrical Plan Drawing RequirementsThe electrical plans submitted pursuant to Rule 535-X-11-.07 of this chapter must:
(a) Provide plan and detail of service equipment, including service entrance, conductors, service raceway and clearances above ground and above structures.(b) Indicate method and detail for ground service equipment.(c) Provide a single line diagram of the entire electrical installation.(d) Provide complete load calculations for service and feeders.(e) Identify and show sizes of all feeders and branch circuits.(f) Show size, rating, and location of main disconnect/over-current protective devices.(g) Detail method of interconnection between modules or units and location of connections.(h) Show location of all outlets and junction boxes.(i) Indicate how nonmetallic-sheathed cable in locations subject to mechanical damage is to be protected.(j) Indicate method of backing mounting and stapling of fixtures and wiring.(k) Provide details showing mounting of nontypical fixtures, if any.(l) Provide name plate rating of all appliances and equipment.(m) Indicate method of testing.(n) Indicate that all wiring, fixtures, and equipment are listed or labeled. Author: Harold A. Hendrix